ANALOG · SCALING

How to Scale a 4–20mA Load Cell Signal in a PLC

A load-cell transmitter does not give you kilograms directly. Convert raw counts to engineering units first.

4–20mALoad CellMUL / DDIV

Signal chain

Hopper Weight→Load Cell mV/V→Transmitter 4–20mA→PLC AI→D300 Raw→D310 kg

Lab Case P-001 uses a training range of D300 = 0–4000 and D310 = 0–5000, where 5000 represents 500.0 kg with one implied decimal place.

Scaling

D310 = (D300 × 5000) / 4000
MUL  D300 K5000 D320
DDIV D320 K4000 D310
D300 rawD310Weight
000.0 kg
8001000100.0 kg
20002500250.0 kg
32004000400.0 kg
40005000500.0 kg

Why feed-rate calculation is more sensitive

At 500 kg over 4000 counts, one count equals 0.125 kg. With a simple two-second difference, a one-count change corresponds to 225 kg/h, so quantization and noise can be magnified.

A short-window difference is not enough by itself. The averaging window, filter, analog update period and post-refill settling time all matter.

The analog module is not final

FX3U-3A-ADP was a compact/cost-focused candidate, not a final approved module. Required dosing accuracy, noise, update rate and AO accuracy still need validation before purchase.

Wiring and filtering checks

  • Shielded twisted pair
  • Single-point grounding
  • Separate analog wiring from VFD power wiring
  • Check transmitter/module digital filtering
  • Verify analog update period vs calculation period
  • Define a post-refill settling interval